Solar Single Line Diagram: What to Show and How to Draw It
October 16, 2026

A solar single line diagram (SLD) shows the electrical path of a PV system with one line per circuit: from the strings through DC isolation, the inverter, AC protection and metering to the point of connection, with a rating against every component. In the UK it goes into the G99 application, the IEC 62446-1 documentation pack and the commissioning file, so it has to match what is actually installed.
In short
- On an SLD one line stands for all conductors of a circuit. A wiring diagram shows every conductor and terminal; the SLD shows ratings and the order of components.
- Every component carries its rating: kWp and string configuration, isolator and fuse ratings, inverter AC output, RCD type, cable sizes and the earthing arrangement.
- Batteries change the drawing. DC-coupled storage sits behind a hybrid inverter; AC-coupled storage has its own inverter and its own AC protection.
- As of October 2026, BS 7671:2018+A4:2026 is the current edition of the Wiring Regulations. Its new Chapter 57 covers stationary batteries.
- On commercial roofs with several inverters, the SLD is where you fix which roof plane feeds which inverter. In one of our projects that meant ten roof planes on four buildings feeding four inverters.
We draw single line diagrams in AutoCAD for installers in the UK and across Europe, from small domestic systems to a 519.61 kWp commercial roof with four 100 kW inverters and a 208.9 kWh battery. Most diagrams that come back from a DNO or a site team do not fail on the drawing itself. They fail because a rating is missing or because the diagram no longer matches the equipment on site. Our AutoCAD solar planning service delivers SLDs as DWG and PDF.
What is a solar single line diagram?
A solar single line diagram is a simplified electrical drawing in which each circuit is drawn as one line, regardless of how many conductors it has. It is the drawing that a DNO engineer, an asset owner or an O&M contractor reads to understand the system in a few minutes: what is connected to what, in which order, and at what rating.
The term is often confused with a solar wiring diagram. Many searches for “solar wiring diagram” come from DIY and off-grid projects, where a picture of cables and terminals is exactly what is needed. On a commercial or MCS installation the two drawings have different jobs.
| Drawing | What it shows | Who uses it |
|---|---|---|
| Single line diagram (SLD) | Components in order, one line per circuit, ratings | DNO, client, commissioning engineer, O&M |
| Wiring diagram | Every conductor, terminal and cable core | Electrician on site |
| Site layout plan | Physical position of array, inverters, cable routes, meter | DNO, installation team |
| String plan | Which module belongs to which string and MPPT | Installation team, commissioning |
What should a solar SLD show?
A solar SLD should show every component from the PV array to the point of connection, each with the rating you would need to replace it. If a value is not on the drawing, the reader has to open a datasheet or ask, and that is where approvals and handovers slow down.
| Section | What to draw | Values to state |
|---|---|---|
| PV array | Strings per MPPT, modules per string | Module power (Wp), Voc and Isc, total kWp |
| DC side | String fuses or combiner boxes where used, DC isolators, surge protection | Voltage and current ratings, SPD type |
| Inverter | Each inverter with its MPPT inputs and phase connection | Make and model, AC output in kW, DC/AC ratio |
| AC side | AC isolator, protective devices, cables | Current ratings, RCD type, cable size |
| Metering | Generation meter, export limitation CT where used | Meter type, CT position |
| Storage | Battery, battery inverter or hybrid inverter | Capacity in kWh, inverter rating, coupling |
| Earthing | Main earthing terminal, bonding, earth electrode where used | Earthing arrangement (TN-C-S, TN-S or TT) |
| Point of connection | Cut-out, main fuse, main meter | Fuse rating, MPAN |
Two values deserve their own line on every diagram: the DC capacity and the inverter AC rating. On a 91 kWp roof we drew 182 modules of 500 W on one inverter rated at 115 kW AC. Both figures matter, and both have to be stated, because the capacity the DNO assesses and the size that decides the application route are not always the same number. What the DNO checks on the SLD in a G99 application is covered in our guide to G99 application drawings.
Earthing is the item most often reduced to a single earth symbol. That is not enough. The diagram should state the earthing arrangement of the supply and show where the PV system is bonded, because the protective measures on the AC side depend on it. Our article on earthing and bonding design for solar PV explains the options.
Which symbols are used on a solar single line diagram?
Solar SLDs in the UK use the graphical symbols of BS EN 60617 (IEC 60617), with a legend on the drawing for anything that is not standard. Consistency matters more than style: the same component should look the same on every sheet of the drawing set.
| Component | Usual representation |
|---|---|
| PV string or array | PV module symbol with the number of modules per string written alongside |
| Inverter | Box with a DC-to-AC conversion symbol, labelled with make, model and kW |
| Isolator | Switch symbol, marked DC or AC with its rating |
| Fuse | Fuse symbol with its rating in A |
| Surge protection device | SPD symbol connected to earth, with type |
| RCD or RCBO | Circuit breaker symbol with residual current element, with type and rating |
| Battery | Battery cell symbol with capacity in kWh |
| Meter and CT | Meter symbol; CT drawn on the conductor it measures |
| Earth | Earth symbol at the main earthing terminal |
How do you draw a single line diagram for a solar PV system with batteries?
Start with the coupling, because it decides the whole layout of the diagram. With DC coupling the battery connects to the DC side of a hybrid inverter and appears behind it. With AC coupling the battery has its own inverter, which connects on the AC side and needs its own isolation and protection.
| On the SLD | DC-coupled battery | AC-coupled battery |
|---|---|---|
| Position of the battery | On the DC side of the hybrid inverter | Behind its own battery inverter on the AC side |
| Inverters shown | One hybrid inverter | PV inverter and battery inverter |
| AC protection | One AC circuit | Separate AC circuit for the battery inverter |
| Capacity to declare | Hybrid inverter rating | PV inverter plus battery inverter |
Two of our projects show both ends of the scale. A 15.64 kWp roof with 34 modules runs on a 15 kW three-phase hybrid inverter with three MPPT inputs and a 9.6 kWh lithium iron phosphate battery, DC-coupled. A 519.61 kWp commercial roof uses four 100 kW string inverters and a 208.9 kWh battery, also coupled on the DC side. The principle is the same; on the larger system the diagram has to show which inverter the battery sits behind.
Storage now has its own chapter in the Wiring Regulations. BS 7671:2018+A4:2026 was published in April 2026 and adds Chapter 57 on stationary secondary batteries, which deals among other things with where batteries may be installed. The previous edition is withdrawn as of October 2026. A summary of the changes is available from BSI. For the DNO, storage also counts towards the declared capacity, so the battery inverter rating belongs on the diagram.
From our projects: four buildings, ten roof planes, one diagram
The situation: A commercial portfolio of 101.92 kWp on four buildings, with 208 modules on ten separate roof planes facing south-east (128°) and north-west (308°). Roof areas ranged from 18 m² to more than 80 m², and the whole portfolio had to feed four inverters.
What we found: The difficult part was not shading but electrical balance. Strings ranged from nine modules on the smallest planes to forty on the largest roof, and each group had to fit an inverter without pushing string voltages or DC/AC ratios out of range.
What we did: We assigned each roof plane to an inverter by proximity and string compatibility. The two smallest roofs, 36 modules in total, went onto a 25 kW inverter at a DC/AC ratio of 105.8 %. The largest roof, 80 modules, went onto a 40 kW inverter at 98 %. One roof with 36 modules on a 15 kW inverter was deliberately oversized to 117.6 %, because its opposing orientations never reach peak output at the same time.
The result: The simulation confirmed a specific yield of 1,027.15 kWh/kWp, a performance ratio of 80.50 % and shading losses of 5.7 % across the portfolio. The lesson for the SLD: the assignment of planes to inverters and each DC/AC ratio belong on the diagram. Without them, the site team has no way to check that the strings were connected the way the design assumed. The full analysis is in our multi-building portfolio case study.
Can you use a solar single line diagram template?
A template is a reasonable starting point for a simple domestic system, but it becomes a risk as soon as it is reused without checking every value. Templates in PDF or DWG save drawing time, and most of the effort on a small system goes into the ratings rather than the lines.
The problems we see with reused templates are predictable: ratings left over from the previous job, a battery drawn AC-coupled when the installed system is DC-coupled, and existing generation on the same supply missing from the drawing. Once a system has more than one inverter, storage or an export limitation scheme, a drawing made for the project is faster than correcting a template. If you prefer to keep the string design in-house, our guide to inverter sizing and configuration covers the values the diagram depends on.
Common mistakes
- Ratings missing: Components drawn without current, voltage or kW values. Fix: state the rating on every device, not only in the cable schedule.
- Diagram not updated after a change: A different inverter or battery is installed, but the SLD still shows the original design. Fix: issue a revised diagram with every equipment change and keep the as-built version in the handover pack.
- Existing generation left out: The DNO assesses the total on the connection. Fix: draw existing PV, batteries and generators on the same supply.
- Export limitation as a note: A text box saying “export limited to 3.68 kW” does not show how. Fix: draw the limiting device and the CT on the conductor it measures.
- Earthing reduced to a symbol: Fix: state the earthing arrangement and show the bonding of the PV system.
If you would rather hand the drawings over, we produce single line diagrams, string plans and site layout plans as part of our AutoCAD drawing service for solar installers, delivered as DWG and PDF.
FAQs
Do I need a single line diagram for a G98 installation?
The G98 notification itself does not require one, but the system documentation does. IEC 62446-1 lists a single line wiring diagram as part of the documentation for a grid-connected PV system, so it belongs in the handover pack. Our guide to IEC 62446-1 as-built documentation lists the rest.
Who draws the single line diagram?
Usually the installer’s designer or an external design office. What matters is that the person drawing it has the final equipment list, because the SLD has to match the application form and the installed system. Many installers outsource it together with the site layout plan.
Should the SLD be delivered as DWG or PDF?
Both. The PDF goes into applications and handover packs; the DWG lets you or the next contractor update the drawing when equipment changes. A diagram that only exists as a PDF is usually redrawn from scratch at the first change.
Can PV*SOL produce a single line diagram?
PV*SOL premium includes a circuit diagram and an overview plan in its project report, which is useful for checking the design. For applications we draw the SLD in AutoCAD, because it needs the point of connection, protective devices and site-specific ratings that the simulation report does not contain.
Does a battery need its own single line diagram?
No. The battery belongs on the same diagram as the PV system, because the DNO and the commissioning engineer need to see how storage and generation share the connection. Show its coupling, capacity in kWh and the inverter it connects through.
Checklist
- Draw the full path from strings to the cut-out, one line per circuit.
- State a rating on every component, including DC capacity and inverter AC output.
- Show battery coupling and existing generation on the same supply.
- Draw export limitation devices and CT positions, not just a note.
- Issue a revised SLD with every equipment change and keep the as-built version in the handover pack.
We draw single line diagrams, string plans and site layout plans for UK installers, delivered as DWG and PDF and matched to your application form.
Author: Heval Arcan, Lion Solar Solutions. As of October 2026.